Local and Serial Port Parameters
Firmware Version 1.01-3.01

Chapter 3

3-6

Parameter 7 Ċ Accel Time 1

Freq

P

R

P

R

Enter

Seconds
0
600
5

Read and Write
Units
Minimum Value
Maximum Value
Factory Setting

This parameter determines the time that it will take the drive to ramp from
0 Hz to the maximum frequency programmed into Parameter 19. The drive
output frequency will accelerate at a linear rate proportional to this setting
for any frequency (speed) change unless one of the following conditions
modify the rate:

Accel Time 2 is selected — see Parameter 30.

The MOPC setting is reached — see Parameter 36.

Dwell frequency is used — see Parameter 43.

Parameter 8 Ċ Decel Time 1

Freq

P

R

P

R

Enter

Seconds
0
600
5

Read and Write
Units
Minimum Value
Maximum Value
Factory Setting

This parameter sets the time that it will take the drive to ramp from the
maximum frequency programmed into Parameter 19 to 0 Hz. The drive
output frequency will decelerate at a linear rate proportional to this setting
for any frequency (speed) change unless one of the following conditions
modify the rate:

Decel frequency hold is selected and a high bus voltage exists — see
Parameter 11.

Decel time 2 is selected — see Parameter 31.