Parameter 54 ċ local input, Parameter 55 ċ remote input – Rockwell Automation 1336VT AC DRIVE 5-300AMP (2-160KW) PROGRAMMING MANUAL User Manual

Page 52

Advertising
background image

Serial Port Parameters
Firmware Version 1.01-3.01

Chapter 4

4-2

Parameter 54 Ċ Local Input

Read Only

Units

Byte

Min Value

0

Max Value

255

This parameter is an eight-bit word that reports the status of the
pushbuttons on an optional Control or Programming and Display Panel.

BIT 1

Start

Jog

Stop

Enter

P

R

BIT 0

BIT 2

BIT 3

BIT 4

BIT 5

BIT 6

BIT 7

0 = Off (not pressed) 1 = On (pressed)

Parameter 55 Ċ Remote Input

Read Only

Units

Byte

Min Value

0

Max Value

255

This parameter is an eight-bit word. Each bit represents the status of the
customer connection to remote terminal block TB3.

BIT 0 — TERM 27 — Select speed

BIT 1 — TERM 28 — Auxiliary

BIT 2 — TERM 26 — SW2

BIT 3 — TERM 24 — SW1

BIT 4 — TERM 22 — Jog

BIT 5 — TERM 23 — Reverse

BIT 6 — TERM 20 — (not) Stop

BIT 7 — TERM 19 — Start

0 = Off (not present) 1 = On (present)