Local and Serial Port Parameter Settings
Firmware Version 1.01-3.01

Chapter 9

9-2

Table 9 -- Parameter List for Parameters 0 to 50 (cont.)

Local

Programming

Serial

Panel

Port

Parameter Parameter

Min/Max

Min/Max

Factory

Number

Text

Units

Values

Values

Setting

30

ACCEL TIME 2

Seconds

0/600

0.00/600.00

5

31

DECEL TIME 2

Seconds

0/600

0.00/600.00

5

32

SKIP FREQUENCY 1

Hertz

0/250

0/250

250

33

SKIP FREQUENCY 2

Hertz

0/250

0/250

250

34

SKIP FREQUENCY 3

Hertz

0/250

0/250

250

35

SKIP FREQUENCY BAND

Hertz

0/15

0/15

0

36

MOPC

% of Rated Output Current

50/115

50/115

115

37

SERIAL BAUD RATE

Code

0/1

0/1

1

38

OVERLOAD CURRENT

% of Rated Output Current

50/115

50/115

100

39

FAULT CLEAR

Off/On

0/1

0/1

1

40

POWER FAULT

Off/On

0/1

0/1

0

41

MOTOR TYPE

Code

0/2

0/2

0

42

SLIP COMPENSATION

Hertz

.0/5.0

0.00/5.00

.0

43

DWELL FREQUENCY

Hertz

0/120

0/120

0

44

DWELL TIME

Seconds

0/10

0/10

0

45

PWM FREQUENCY

kHZ

.40/2.00

0.40/2.00

.40

46

PULSE SCALE FACTOR

Ratio

1/255

1/255

64

47

LANGUAGE

Code

0/5

0/5

0

48

START BOOST

Volts

0/115

0/115

0

49

BREAK FREQ

Hertz

0/120

0/120

0

50

BREAK VOLTS

Volts

0/230

0/230

0