Parameter 24 ċ jog frequency, Parameter 25 ċ analog output – Rockwell Automation 1336VT AC DRIVE 5-300AMP (2-160KW) PROGRAMMING MANUAL User Manual

Page 32

Advertising
background image

Local and Serial Port Parameters
Firmware Version 1.01-3.01

Chapter 3

3-18

Parameter 24 Ċ Jog Frequency

Freq

P

R

P

R

Enter

Hertz
.0
120
.0

Read and Write
Units
Minimum Value
Maximum Value
Factory Setting

The value of this parameter is the speed reference frequency used when jog
is commanded. Any time jog is commanded, the drive will ramp to this
frequency. Upon removing the jog command, if no other motion command
is present, the drive will follow the stopping mode selected in Parameter
10. This parameter may be lower than the Minimum Frequency set by
Parameter 16, but will be limited by the Maximum Frequency set by
Parameter 19.

Parameter 25 Ċ Analog Output

Freq

P

R

P

R

Enter

Code
0
1
0

Read and Write
Units
Minimum Value
Maximum Value
Factory Setting

This parameter selects which one of the two possible output signals are
used as the meter output at TB2, Terminal 9.

When set to 0, the meter output is proportional to the actual output
frequency of the drive.

When set to 1, the meter output is proportional to the % of drive load
current.

Important: The displayed load current is an approximate value calculated
from drive internal feedback. Motor characteristics will affect the accuracy
of the load current indication.