Local and Serial Port Parameters
Firmware Version 1.01-3.01

Chapter 3

3-17

Parameter 22 Ċ Local Reverse

Freq

P

R

P

R

Enter

Off/On
0
1
1

Read and Write
Units
Minimum Value
Maximum Value
Factory Setting

Parameter 22 selects the source that determines the direction of motor
rotation.

When set to 0, the direction of rotation is controlled by either the status of
the reverse input at TB3 or through serial communications. The direction
pushbutton on an optional Control Panel is not functional, but the direction
LED display on the Control Panel is functional.

When set to 1, the direction of rotation is controlled by the Control Panel
direction pushbutton. Other sources of reversing control are disabled, and
the direction of rotation cannot be changed by inputs from TB3 or through
serial communications.

Parameter 23 Ċ Local Jog

Freq

P

R

P

R

Enter

Off/On
0
1
1

Read and Write
Units
Minimum Value
Maximum Value
Factory Setting

Parameter 23 determines if an optional Control Panel jog pushbutton can
jog the drive. The setting of this parameter will not disable jog commands
from other sources and will not disable other functions on the Control
Panel.

When set to 0, the Control Panel jog function is disabled. The jog
pushbutton on an optional Control Panel will have no affect, but the jog
input at TB3 or serial communication command can jog the drive.

When set to 1, the Control Panel jog function is enabled. The jog
pushbutton on the Control Panel will jog the drive as long as it is pressed.
Other sources of control will still be functional and jog inputs from TB3 or
serial communications can jog the drive.