Local and Serial Port Parameters
Firmware Version 1.01-3.01

Chapter 3

3-28

Parameter 39 Ċ Fault Clear

Freq

P

R

P

R

Enter

Off/On
0
1
1

Read and Write
Units
Minimum Value
Maximum Value
Factory Setting

This parameter determines the sequence of events required to clear a Fault
Code at the drive. The setting of Parameter 14, Auto Restart, will affect the
sequence required to reset the drive after a fault has occurred. The setting
of Parameter 40, Power Fault, will affect the sequence required to reset the
drive after an AC 3-phase line power interruption has occurred.

If set to 0, a Fault Code can only be cleared by removing input power from
the drive, letting the bus discharge, then reapplying input power.

If set to 1, a Fault Code can be cleared by either removing input power
from the drive, letting the bus discharge then reapplying input power, or by
causing the stop signal from an optional Control Panel or Terminal 20 of
TB3 on the Logic Interface Board (MOD-L1, L2 or L3) to go false then
true with a maintained false Start command.

If MOD-G2 Serial Communications, is being used, toggling the discrete
stop bit will not perform this function, refer to Parameter 51.