Parameter 65 ċ command frequency, Parameter 66 ċ output frequency, Parameter 67ċ output pulses – Rockwell Automation 1336VT AC DRIVE 5-300AMP (2-160KW) PROGRAMMING MANUAL User Manual

Page 62: Parameter 68 ċ serial password, Parameter 69 ċ reverse status

Advertising
background image

Serial Port Parameters
Firmware Version 1.01-3.01

Chapter 4

4-12

Parameter 65 Ċ Command Frequency

Read Only

Units

Hertz

Min Value

0.00

Max Value

250.00

This parameter represents the present drive command frequency set by the
current command source. The current command source will be indicated by
a code from 0-9 and shown by selecting Parameters 5 or 6.

Parameter 66 Ċ Output Frequency

Read Only

Units

Hertz

Min Value

0.00

Max Value

250.00

This parameter represents and will display the actual output frequency of
the drive and will change as programmed parameters interact with the
Command Frequency, Parameter 65. It is used in the PLC Controller
Discrete Transfer.

Parameter 67Ċ Output Pulses

Read Only

Units

1 Rev/256

Min Value

0

Max Value

65535/256

This parameter represents the angular position of the output waveform to 1
in 256 parts of an output cycle. It will continually increment from 0 to
65535 or 65535 to 0, then repeat as long as the drive is running.

Parameter 68 Ċ Serial Password

Read and Write

Units

Code

Min Value

0

Max Value

9999

Factory Setting

0

This parameter stores the access code used with the remote handheld
programming device and is not intended to be used with remote I/O board
programming. Once set, you can read the password only through RIO
board programming.

Parameter 69 Ċ Reverse Status

Read and Write

Units

Code

Min Value

0

Max Value

1

Factory Setting

0