Serial Port Parameters
Firmware Version 1.01-3.01

Chapter 4

4-4

Parameter 56 Ċ Serial Input

BIT 4 — Jog

0 = select (not) Jog — continue last state

(cont.)

1 = select Jog at Jog Frequency, Parameter 24

BIT 5 — Direction

0 = select Forward

1 = select Reverse

BIT 6 — Stop

0 = select Stop

1 = select (not) Stop — continue last state

BIT 7 — Start

0 = select (not) Start — continue last state

1 = select Start

!

ATTENTION: Unexpected machine motion can cause injury or
death. Do not use a Local or Remote Control Panel with option G2
or in any maintained serial control start application.

A maintained start input from the Serial Input Byte (Par 56, BIT 7)
will affect Control Panel stop pushbutton operation. The drive will
automatically restart after the Control Panel stop pushbutton is
depressed and released.