Parameter 49 ċ break frequency, Parameter 50 -- break volts – Rockwell Automation 1336VT AC DRIVE 5-300AMP (2-160KW) PROGRAMMING MANUAL User Manual

Page 50

Advertising
background image

Local and Serial Port Parameters
Firmware Version 1.01-3.01

Chapter 3

3-36

Parameter 49 Ċ Break Frequency

Freq

P

R

P

R

Enter

Hertz
0
120
0

Read and Write
Units
Minimum Value
Maximum Value
Factory Setting

This parameter sets an intermediate frequency below Parameter 17
(Base Frequency), if Parameter 9 is set to 11. This parameter along with
Parameters 48 and 50 are used to construct a custom volts-per-hertz curve.

Parameter 50 -- Break Volts

Freq

P

R

P

R

Enter

Volts
0
230
0

Read and Write
Units
Minimum Value
Maximum Value
Factory Setting

Important: If Parameter 50 is less than Parameter 48, the drive will fault
and display F35 –– Negative Slope.

This parameter sets an intermediate voltage below Parameter 18 (Base
Volts), if Parameter 9 is set to 11. This parameter along with Parameters 48
and 49 are used to construct a custom volts-per-hertz curve. This parameter
setting should not be less than Parameter 48.