Parameter 26 Ċ Preset/2

nd

Accel

Freq

P

R

P

R

Enter

Code
0
1
0

Read and Write
Units
Minimum Value
Maximum Value
Factory Setting

This parameter selects which drive function will be controlled by optional
inputs SW1, SW2, Speed Select at terminal block TB3 and Parameter 72,
Activate Parameters 73-76.

Important: The settings of Serial Input (Parameter 56) and Serial Mask
(Parameter 57) will affect the selection of Preset Frequencies 1, 2, 3, 4, 5, 6
and 7. Bits 2 and 3 of Parameter 56 select the source for drive preset speed
control. Bits 0 and 1 of Parameter 56 select the source for drive accel and
decel control.

If Parameter 26 is set to 0, accel and decel times will be set by Accel Time
1 (Parameter 7) and Decel Time 1 (Parameter 8). SW1, SW2, Speed Select
and Parameter 72 will control the selection of Preset Frequencies as
follows:

Accel at Accel Time 1, Parameter 7

Speed

Parameter

Decel at Decel Time 1, Parameter 8

SW1

SW2

Select

72

Run at:

False

False

False

Off

Frequency Select 1, Parameter 5

True

False

False

Off

Preset Frequency 1, Parameter 27

False

True

False

Off

Preset Frequency 2, Parameter 28

True

True

False

Off

Preset Frequency 3, Parameter 29

False

False

True

Off

Frequency Select 2, Parameter 6

True

False

True

Off

Preset Frequency 1, Parameter 27

False

True

True

Off

Preset Frequency 2, Parameter 28

True

True

True

Off

Preset Frequency 3, Parameter 29

False

False

False

On

Frequency Select 1, Parameter 5

True

False

False

On

Preset Frequency 1, Parameter 27

False

True

False

On

Preset Frequency 2, Parameter 28

True

True

False

On

Preset Frequency 3, Parameter 29

False

False

True

On

Preset Frequency 4, Parameter 73

True

False

True

On

Preset Frequency 5, Parameter 74

False

True

True

On

Preset Frequency 6, Parameter 75

True

True

True

On

Preset Frequency 7, Parameter 76

Important: The settings of Serial Input (Parameter 56) and Serial Mask
(Parameter 57) will affect the selection of Accel Times 1 and 2. Bits 0 and
1 of Parameter 56 select the source for drive accel and decel control. Bits 2
and 3 of Parameter 56 select the source for drive preset speed control.