Chapter – Rockwell Automation 1336VT AC DRIVE 5-300AMP (2-160KW) PROGRAMMING MANUAL User Manual

Page 82

Advertising
background image

11

Chapter

11-1

Local and Serial Port Parameter Settings

Firmware Version 2.01 and 3.01

Table 11 -- Parameter List for Parameters 70 to 89

Parameters 70 to 89

are local and serial port parameters that may only be

accessed with Firmware Version 2.01 and 3.01.

Local

Programming

Serial

Panel

Port

Parameter Parameter

Min/Max

Min/Max

Factory

Number

Text

Units

Values

Values

Setting

70

BASE DRIVER BOARD VERSION

Code

---

---

---

71

CONTROL BOARD VERSION

Code

---

---

---

72

ACTIVATE PARAMETERS 73Ć76

Off/On

0/1

0/1

0

73

PRESET FREQUENCY 4

Hertz

.0/250

0.00/250.00

.0

74

PRESET FREQUENCY 5

Hertz

.0/250

0.00/250.00

.0

75

PRESET FREQUENCY 6

Hertz

.0/250

0.00/250.00

.0

76

PRESET FREQUENCY 7

Hertz

.0/250

0.00/250.00

.0

77

ABOVE FREQUENCY CONTACT Hertz

0/250

0/250

0

78

TRAVERSE PERIOD

Seconds

0/30

0.00/30.00

0

79

MAXIMUM TRAVERSE

Hertz

.0/100

0.00/100.00

.0

80

INERTIA COMPENSATION

Hertz

.0/20.0

0.00/20.00

.0

81

SOFT START/STOP ENABLE

Off/On

---

---

---

82

AMP LIMIT FAULT ENABLE

Off/On

0/1

0/1

0

83

RUN BOOST

Volts

0/115

0/115

0

84

ANALOG INVERSE

Off/On

0/1

0/1

0

85

RESTART TRIES

Code

0/9

0/9

0

86

FAULT BUFFER 0

Code

0/37

0/37

87

FAULT BUFFER 1

Code

0/37

0/37

---

88

FAULT BUFFER 2

Code

0/37

0/37

---

89

FAULT BUFFER 3

Code

0/37

0/37

---