Rockwell Automation 1336VT AC DRIVE 5-300AMP (2-160KW) PROGRAMMING MANUAL User Manual

Page 55

Advertising
background image

Serial Port Parameters
Firmware Version 1.01-3.01

Chapter 4

4-5

Parameter 57 Ċ Serial Mask

Read and Write

Units

Byte

Min Value

0

Max Value

255

Factory Setting

0

This parameter permits the masking of any one of the bits defined in
Parameter 56. Each bit in this parameter must be set to 1 to allow the
corresponding bit in Parameter 56 to be fully functional.

Important: If power is removed from the drive, a default state will occur
resetting all bits in Parameter 57 to 0.

BIT 0 — Decel Time

0 = use SW2 at terminal block TB3 to

select Decel Time 1 or 2. Bit 0 of
Parameter 56 ignored.

1 = use bit 0 of Parameter 56 to select

Decel Time 1 or 2. SW2

at

terminal block TB3

i

gnored.

BIT 1 — Accel Time

0 = use SW1 at terminal block TB3 to

select Accel Time 1 or 2. Bit 1 of
Parameter 56 ignored.

1 = use bit 1 of Parameter 56 to select

Accel Time 1 or 2. SW2 at
terminal block TB3 ignored.

BIT 2 — Frequency Control

0 = use SW2 at terminal block TB3 to

select Preset Frequency 1-7. Bit 2
of Parameter 56 ignored.

1 = use bit 2 of Parameter 56 to select

Preset Frequency 1-7. SW2 at
terminal block TB3 ignored.

BIT 3 — Frequency Control

0 = use SW1 at terminal block TB3 to

select Preset Frequency 1-7. Bit 3
of Parameter 56 ignored.

1 = use bit 3 of Parameter 56 to select

Preset Frequency 1-7. SW1 at
terminal block TB3 ignored.

Advertising