Parameter 83 -- run boost, Parameter 9 = 12 -- run and start boost – Rockwell Automation 1336VT AC DRIVE 5-300AMP (2-160KW) PROGRAMMING MANUAL User Manual

Page 70

Advertising
background image

Local and Serial Port Parameters
Firmware Version 2.01-3.01

Chapter 5

5-7

Parameter 83 -- Run Boost

Freq

P

R

P

R

Enter

Volts
0
115
0

Read and Write
Units
Minimum Value
Maximum Value
Factory Setting

Important: If Run Boost is greater than Start Boost (Parameter 48), the
drive will fault and display F34 –– Boost Error.

0

300V AC

100V AC

200V AC

400V AC

500V AC

10 Hz

30 Hz

50 Hz

60 Hz

80 Hz

100 Hz

20 Hz

40 Hz

70 Hz

90 Hz

4

1 Parameter 83 Run Boost = 66 Volts

2 Parameter 48 Start Boost = 100 Volts

3 Parameter 17 Base Frequency = 60 Hertz
Parameter 18 Base Volts = 460 Volts

4 Parameter 19 Maximum Frequency = 100 Hertz
Parameter 20 Maximum Volts = 460 Volts

3

2

1

Parameter 9 = 12 -- Run and Start Boost

When Parameter 9 is set to 12 and this parameter is set to a value less than
Start Boost but greater than zero, Run Boost will be enabled. Run Boost
allows a secondary lower boost voltage to be used once the drive has
reached command speed and the motor is no longer accelerating. When the
motor is decelerating, the drive will use Run Boost, not Start Boost to
reach the new command speed.