Local and Serial Port Parameters
Firmware Version 1.01-3.01

Chapter 3

3-13

Parameter 15 Ċ Factory Set

Freq

P

R

P

R

Enter

None
0
0
0

Read and Write
Units
Minimum Value
Maximum Value
Factory Setting

This parameter may be viewed but should not be changed from its factory
setting.

Parameter 16 Ċ Minimum

Frequency

Freq

P

R

P

R

Enter

Hertz
0
120
0

Read and Write
Units
Minimum Value
Maximum Value
Factory Setting

This parameter sets the minimum drive operating frequency. The only
running conditions that can override the minimum frequency setting are
Jog Frequency (Parameter 24) or Dwell Frequency (Parameter 43).
Minimum Frequency also sets the offset or starting point for analog
response signals. These include the local and remote potentiometers that
may be used to control the drive output frequency. Minimum Frequency is
produced at a potentiometer setting of zero. Minimum Frequency will also
be produced with a voltage input of zero or a current input of 4mA unless
Parameter 84, Analog Inverse is set to 1.