DeviceNet Objects (Class Code 0x0F — Parameter Object)

C-11

Instance Attributes

Attribute ID

Access Rule

Stub/Full

Name

Data Type

Description

1

Stub

Parameter Value

Specified in

Descriptor,

Data Type and

Data Size
attributes.

Actual value of parameter. Data type specified
in descriptor, data type, and data size.

➀➁

2

Get

Stub

Link Path Size

USINT

Size of Link Path attribute. If this attribute is 0,
then no link is specified.
Number of BYTEs in attribute 3.

3

Get

Stub

Link Path

ARRAY of path

segments

Path to the object from where this parameter
value is retrieved.
The link path is limited to 255 BYTEs.

Segment type/port

BYTE

Segment Address

Path (format

depends on

data contained

in segment

type/port)

4

Get

Stub

Descriptor

WORD

Descriptor of parameter. Refer to the table on
page C-12.

5

Get

Stub

Data Type

USINT

Data type code. Refer to the table on
page C-13.

6

Get

Stub

Data Size

USINT

Number of BYTEs in attribute 1, Parameter
Value.

7

Get

Full

Parameter Name
String

SHORT_

STRING

A text string representing the parameter
name. For example, “frequency #1.”
The maximum number of characters is 16.
(The first byte is a length code.)

8

Get

Full

Units String

SHORT_

STRING

Engineering unit string.
The maximum number of characters is 4.
(The first byte is a length code.)

9

Get

Full

SHORT_

STRING

The maximum number of characters is 64.
(The first byte is a length code.) Always
returns 0.

10

Get

Full

Minimum Value

Same as

attribute 1

The minimum valid actual value to which
attribute 1, Parameter Value can be set.

11

Get

Full

Maximum Value

Same as

attribute 1

The maximum valid actual value to which
attribute 1, Parameter Value can be set.

12

Get

Full

Default Value

Same as

attribute 1

The actual value attribute 1, Parameter Value
should be set to when the user wants the
default for the parameter.

13

Get

Full

Scaling Multiplier

UINT

Multiplier for scaling formula.

14

Get

Full

Scaling Divisor

UINT

Divisor for scaling formula.

15

Get

Full

Scaling Base

UINT

Base for scaling formula.

The access rule is defined in bit 4 of instance attribute 4, the Descriptor. If bit 4 is 0 the access rule is Set and the Parameter Value can be read and
written. If bit 4 is 1, the access rule is Get and the Parameter Value can only be read.

Data type specified in instance attributes 4 (Descriptor), 5 (Data Type) and 6 (Data Size).