background image

DeviceNet Objects (Class Code 0x97 — SCANport Pass-Through Fault Object)

C-21

Class Code 0x97 — SCANport
Pass-Through Fault Object

The SCANport Pass-Through Fault Object provides information on
the product’s fault queue.

Class Attributes

Instance Attributes

Attribute ID

Access Rule

Name

Data Type

Description

0

Set

Write Fault Command

BYTE

1 = Clear Faults
2 = Clear Fault Queue
3 = Reset Product

1

Get

Read Number of Fault
Queue Entries

BYTE

Reads the number of fault queue entries.

2

Get

Read Fault Queue Trip
Index

BYTE

Reads the index of the fault that tripped the product.

Attribute ID

Access Rule

Name

Data Type

Description

0

Get

Read Fault Queue Entry
Full/All Info

STRUCT of

Fault Text

ARRAY of BYTE

16 character string (no length information, no
terminating null).

Fault Code

WORD

Fault Code.

Fault Time Stamp

STRUCT

BYTE

1/100 Second (0 – 99).

BYTE

Second (0 – 59).

BYTE

Minute (0 – 59).

BYTE

Hour (0 – 23).

BYTE

Day of Week (0 – 6).

BYTE

Date (1 – 31).

BYTE

Month (1 – 12).

BYTE

Year (0 – 99

).

128

Get

Fault Code and Time
Stamp

STRUCT of

Fault Code

WORD

Fault Code.

Fault Time Stamp

STRUCT of

BYTE

1/100 Second (0 – 99).

BYTE

Second (0 – 59).

BYTE

Minute (0 – 59).

BYTE

Hour (0 – 23).

BYTE

Day of Week (0 – 6).

BYTE

Date (1 – 31).

BYTE

Month (1 – 12).

BYTE

Year (0 – 99

).

129

Get

Read Fault Text String
Only

ARRAY of BYTE

16 character string (no length information, no
terminating null).

Sunday is a value of zero.

Year is an offset from 1990.

Advertising