Configuring a Scanner to Communicate with the 1203-GK5 Module or 1336-GM5 Board

4-11

10. Under Polled, set the following:

11. Click OK. A DeviceNet Manager message appears.

12. Click Yes. The 1771-SDN Scan List Editor: Both Channels

dialog box reappears.

13. Click Auto Map to display the Auto Map Options dialog box.

Figure 4.18
Auto Map Options Dialog Box

14. Select the following:

Refer to the DeviceNet Manager online help for more
information.

Box

Setting

Enable

Select it. An X appears in it.

Polled Size

Type the number of bytes the adapter receives in the RX box
and the number of bytes it transmits in the TX box.
Important: To determine the number of bytes, use the
following equation:
4 + (number of datalinks enabled x 4) = total bytes
For example, if all four datalinks are enabled, you would type
20 in these boxes:
4 + (4 x 4) = 20.

Poll Rate

Select either every scan or background as a poll rate.

Box

Setting

Input Block Xfer

Select the location in the PLC to which messages from the
1203-GK5 module or 1336-GM5 board are sent.

Output Block Xfer

Select the location in the PLC from which messages to the
1203-GK5 module or 1336-GM5 board are sent.

Mapping Method

Select the mapping method.