F-17

Message Operation

Fault Queue Entry Read Full reads the contents of the fault queue
specified in word 3 of the request. The response returns the fault text
which can be ASCII text. Every two characters of text are in reverse
order. Also, the 1336 FORCE drive returns a time stamp, indicating
the day and time the fault occurred.

If an error has occurred, word 1 of the response returns a negative
value.

Example

In this example, Fault Queue Entry number 3 was retrieved from a
1336 PLUS drive. The drive response returned the ASCII text Drive
Reset Flt
, with each character reversed. The fault code for this
example is 22.

Data File Format

* Example only — These values vary depending on parameters and products.

0

1

2

3

4

5

6

7

8

9

PLC request

3

1792

3*

Drive response

18

1792

3*

29252*

20313*

8293*

25938*

25971*

8308*

27718*

8303*

22*

Drive response

\00\12

\07\00

\03\00

r D

v i

e

e R

e s

t

l F

t

\00\16