Appendix

A

Specifications

Appendix Objectives

Appendix A provides the specifications that you may need to install
or use either the 1203-GK5 module or the 1336-GM5 board. These
adapters are non-repairable units. If they are broken, you must replace
the whole unit.

DeviceNet Conformance Tested

Both the 1203-GK5 module and 1336-GM5 board are DeviceNet
Conformance Tested.

1203-GK5 Module Specifications

The following table gives the specifications for the 1203-GK5
DeviceNet communications module.

Inrush current may be four times the input current for 5 ms.

Category

Specifications

Electrical

Input Voltage
Input Current
SCANport Load

12 to 25 V DC
110 mA

60 mA DC

Environmental

Operating Temperature
Storage Temperature
Relative Humidity

0 to +50

°C (32 to 122°F)

–40 to +85

°C (–40 to 185°F)

0 to 95% non-condensing

Communications

DeviceNet

Baud Rates
Distance Maximum

125, 250, 500 k BPS
500 m (1640 ft.) @ 125 k BPS
200 m (820 ft.) @ 250 k BPS
100 m (328 ft.) @ 500 k BPS

Mechanical

Height
Width
Depth
Enclosure
DIN Rail Standard

76 mm (3.0 in.)
45 mm (1.8 in.)
123 mm (4.8 in.)
NEMA Type 1 (IP30)
35 mm x 7.5 mm (1.38 in. x 0.30 in.)