Fault queue entry read full, Plc block transfer emulation instruction data – Rockwell Automation 1203-GK5 DeviceNet Communications Module FRN 1.xxx-3.xxx User Manual

Page 136

Advertising
background image

F-16

Supported Emulated Block Transfer Commands (Fault Queue Entry Read Full)

Fault Queue Entry Read Full

Fault Queue Entry Read Full reads the contents of the specified
fault queue entry. A message is returned which includes the fault text
and fault code associated with the specified fault queue entry. The
1336 FORCE drive also returns the time stamp associated with the
fault.

PLC Block Transfer Emulation Instruction Data

PLC request instruction length: 3 words
Drive response instruction length: 12 or 16 words

Figure F.10
Message Structure

Header

Word 0

PLC Decimal Value

1792

Header

Word 1

Header

Word 2

PLC Request

Header Word 0

Header Word 1

Header Word 2

Message Length

Message Length

PLC Decimal Value

Fault Queue

Drive Response

Fault Queue

3

Entry Number

18

Data

Word 3

Fault Text

Char 2

Char 1

Data

Word 4

Char 4

Char 3

Data

Word 5

Char 6

Char 5

Data

Word 6

Char 8

Char 7

Data

Word 7

Char 10

Char 9

Data

Word 8

Char 12

Char 11

Data

Word 9

Char 14

Char 13

Data

Word 10

Char 16

Char 15

1792 — Message OK

–30976 — Message Error

Entry Number

Data

Word 11

Fault Code Value

Data

Word 12

Clock

SES

REF

Data

Word 13

Hour

Minute

Data

Word 14

Date

Day

Data

Word 15

Year

Month

1336 FORCE

Drive Only

Time