6-4

Using DeviceNet Explicit Messages

Messaging for the 1747-SDN
Scanner

The SLC copies an Explicit Message into the scanner’s M0-file.
When the copy is completed the scanner moves the message into a
queue for processing. Up to 10 Explicit Messages can be in this
queue.

When the scanner receives a response message it is placed into a
queue. The first response in the queue is available from the M1-file.
When the message delete command is copied into the scanner the
message is complete and the next available response will appear in
the M1-file.

The format of Request and Response messages is in Figure 6.2.

Figure 6.2
Format of DeviceNet Messages

For information on M-File locations, refer to the 1747-SDN
DeviceNet Scanner Module Manual
, Publication 1747-5.8.

The message buffer is composed of two sections:

Transaction header — three words that contain information
identifying the message transaction.

Transaction body — in a request, this contains the DeviceNet
Class, Instance, Attribute and Service Data portions of the
transaction. In a response, this contains the Service Data only.

Format of 32-word M0-file

Write of Explicit Message Request

Format of 32-word M1-file

Read of Explicit Message Response

15

0

15

0

Transaction
Header (3 words)

TXID

COMMAND

TXID

STATUS

word 0

PORT

SIZE

PORT

SIZE

SERVICE

MAC ID

SERVICE

MAC ID

CLASS

SERVICE RESPONSE DATA

Transaction Data
(up to 29 words)

INSTANCE

"

ATTRIBUTE

"

SERVICE DATA

"

"

"

word 31