Devicenet network status led – Rockwell Automation 1203-GK5 DeviceNet Communications Module FRN 1.xxx-3.xxx User Manual

Page 82

Advertising
background image

7-2

Troubleshooting

DeviceNet Network Status LED

The LED closest to the DeviceNet connector is the DeviceNet Status
LED. It is labeled “NET.” Refer to the following table:

LED status

State:

Indicates

Action:

off

Not powered/Not
online

No power/Duplicate ID
not completed

1. Verify that the network power supply is connected and

that power is reaching the adapter through the
connector.

2. Verify that one or more nodes are communicating on

the network.

3. Verify that at least one other node on the network is

operational at the same time and data rate as the
adapter.

flashing green

Online/Not connected

Passed duplicate
ID/No connection
established

No action needed. The LED is flashing to signify that
there are no open communication connections between
the adapter and any other device. Any connection (I/O or
explicit message) made to the adapter over DeviceNet
will cause the LED to stop flashing and remain steady on
for the duration of any open connection.

steady green

Online/Connected

One or more
connections
established

No action needed.

flashing red

Online/Time-out

I/O connection timed
out

1. Connect the controller to the network.
2. Reduce traffic or errors on the network so that

messages can get through within the necessary time
frame.

steady red

Network failure

Failed Duplicate ID or
Bus-off

1. Verify that all nodes have unique addresses.
2. If all node addresses are unique, examine network for

correct media installation.

Advertising