Rockwell Automation 1203-GK5 DeviceNet Communications Module FRN 1.xxx-3.xxx User Manual

Page 76

Advertising
background image

6-8

Using DeviceNet Explicit Messages

In this example, there were four entries in the fault queue. Notice the
following about the data:

Refer to Appendix C, DeviceNet Objects, for more information on
object descriptions.

Location

Value

Meaning

N30:0

0x0201

TXID of 2. Command 1 (Execute)

N30:1

0x0006

Port 0. Size = 6 bytes (N30:3 – 5)

N30:2

0x0E03

Service E (Get Attribute Single) Node 3

N30:3

0x0097

SCANport Pass-Through Fault Object

N30:4

0x0000

Instance 0 (Class Access)

N30:5

0x0001

Attribute 1 (Number of Fault Queues)

N30:70

0x0201

TXID of 2. Status 1 (Success)

N30:71

0x0006

Port 0. Size = 6 bytes (N30:3 – 5)

N30:72

0x8E03

Service 8E (Get Attribute Single Response)

N30:73

0x0004

4 fault queues

Advertising
This manual is related to the following products: