Rockwell Automation 1203-GK5 DeviceNet Communications Module FRN 1.xxx-3.xxx User Manual

Page 78

Advertising
background image

6-10

Using DeviceNet Explicit Messages

The following table display data sent to and received from the
scanner. Values are in hexadecimal.

In this example, there were four entries in the fault queue. Notice the
following about the data:

Refer to Appendix C, DeviceNet Objects, for more information on
object descriptions.

Offset

0

1

2

3

4

5

6

7

8

9

N20:0

4

0

0

0

0

0

0

0

0

0

N20:10

201

6

E03

97

0

1

0

0

0

0

N20:20

0

0

0

0

0

0

0

0

0

0

N20:30

0

0

0

0

0

0

0

0

0

0

N20:40

0

0

0

0

0

0

0

0

0

0

N20:50

201

6

8E03

4

0

0

0

0

0

0

N20:60

0

0

0

0

0

0

0

0

0

0

N20:70

0

0

0

0

0

0

0

0

0

0

N20:80

0

0

Location

Value

Meaning

N20:10

0x0201

TXID of 2. Command 1 (Execute)

N20:11

0x0006

Port 0. Size = 6 bytes (N20:13 – 15)

N20:12

0x0E03

Service E (Get Attribute Single) Node 3

N20:13

0x0097

SCANport Pass-Through Fault Object

N20:14

0x0000

Instance 0 (Class Access)

N20:15

0x0001

Attribute 1 (Number of Fault Queues)

N20:50

0x0201

TXID of 2. Status 1 (Success)

N20:51

0x0006

Port 0. Size = 6 bytes (N20:53 – 55)

N20:52

0x8E03

Service 8E (Get Attribute Single Response) Node 3

N20:53

0x0004

4 fault queues