Configuring the 1203-GK5 Module or 1336-GM5 Board

2-7

Setting the Fault Response Configuration Switches

DIP switches 8 through 6 on SW1 let you configure how a 1203-GK5
module or 1336-GM5 board controls a product when network
communications fail or the scanner is idle. With the factory-default
setting, the product is faulted when communications are disrupted.

Figure 2.6
Setting the Fault Configuration

To edit how the 1203-GK5 or 1336-GM5 responds when network
communications are disrupted, you need to:

1. Refer to the following table to determine the switch settings for

SW 1-8:

2. Refer to the following table to determine the switch settings for

SW 1-7:

3. If you set SW 1-8 or SW 1-7 to 1, select how the module or board

responds when a condition that normally causes a fault occurs:

Off = 0
On = 1

Use DIP switches 8
through 6 for setting
the fault reactions of
the adapter.

!

ATTENTION: Risk of severe bodily injury or
equipment damage exists. These switches allow the user
to change the default configuration that would fault the
drive if communication is lost. Precautions should be
taken to ensure that settings for these switches do not
create a hazard of bodily injury or equipment damage.

Fault on Program/Idle

SW1-8

Enable

0

Disable

1

Fault on Communications Loss

SW1-7

Enable

0

Disable

1

Function

SW1-6

Zero data

0

Hold last state

1