Setting the node address – Rockwell Automation 1203-GK5 DeviceNet Communications Module FRN 1.xxx-3.xxx User Manual

Page 24

Advertising
background image

2-4

Configuring the 1203-GK5 Module or 1336-GM5 Board

Setting the Node Address

DIP switches 6 through 1 on SW2 set the node address for the
1203-GK5 module or 1336-GM5 board. The factory-default setting is
DeviceNet node address 63.

Figure 2.3
Setting the Node Address

To edit the node address, you need to:

1. Refer to the following table to determine the switch settings:

2. Slide switches 6 through 1 to their appropriate positions.

Important: DIP switch and parameter settings take effect when a
module or board first receives power. When you change a setting, you
must remove and then reapply power for the new setting to take
effect.

Off = 0
On = 1

Use DIP switches 6
through 1 for setting
the node address.

DeviceNet

Address

Switch Setting

6 <---- 1

DeviceNet

Address

Switch Setting

6 <---- 1

DeviceNet

Address

Switch Setting

6 <---- 1

DeviceNet

Address

Switch Setting

6 <---- 1

0

000000

16

010000

32

100000

48

110000

1

000001

17

010001

33

100001

49

110001

2

000010

18

010010

34

100010

50

110010

3

000011

19

010011

35

100011

51

110011

4

000100

20

010100

36

100100

52

110100

5

000101

21

010101

37

100101

53

110101

6

000110

22

010110

38

100110

54

110110

7

000111

23

010111

39

100111

55

110111

8

001000

24

011000

40

101000

56

111000

9

001001

25

011001

41

101001

57

111001

10

001010

26

011010

42

101010

58

111010

11

001011

27

011011

43

101011

59

111011

12

001100

28

011100

44

101100

60

111100

13

001101

29

011101

45

101101

61

111101

14

001110

30

011110

46

101110

62

111110

15

001111

31

011111

47

101111

63

111111