Parameters in the 1203-GK5 Module and 1336-GM5 Board

Parameters

The following table provides information on the parameters in the
1203-GK5 module and 1336-GM5 board.

Important:

When accessing this parameter set

through the

DeviceNet Parameter Class, add

the adapter parameter number to

the number of the last parameter of the SCANport device.

When

accessing this parameter set

through the vendor-specific SCANport

Variables-Linear Class, add the adapter parameter number to 0x4000.

.

1 DN-SW1 Setup

Displays the switches settings onSW1.

Important: The present settings may not be the condition under which
the module is operating. They will be the values that are read after a
SCANport/DeviceNet power cycle.

Refer to Chapter 2, Configuring the 1203-GK5 Module or 1336-GM5
Board
, for more information.

Parameter Number

1

Parameter Type

Read Only

Factory Default

0000 0000

Power Cycle Required

No

Datalink A Enabled
Datalink B Enabled
Datalink C Enabled
Datalink D Enabled
Not Used
Hold Last State/Zero Data
Disable Comm Loss Fault
Disable Pgm/Idle Fault

Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1

2 DN-SW2 Node Adx

Displays the node address as it is set on SW2, switches 1 through 6.

Important: This setting is not the setting used by the adapter if either
of the following conditions is true:

• The switches were reset and the adapter was not power cycled.

• Switches 7 and 8 on SW2 are both set to on, so the adapter reads

the node address from parameter 4.

Refer to Chapter 2, Configuring the 1203-GK5 Module or 1336-GM5
Board
, for more information.

Parameter Number

2

Parameter Type

Read Only

Factory Default

63

Minimum Value

0

Maximum Value

63

Power Cycle Required

No

3 DN-SW2 Data Rate

Displays the Data Rate as it is set on SW2, switches 7 and 8.

Important: This setting is not the setting used by the adapter if either
of the following conditions is true:

• The switch was reset and the adapter was not power cycled.

• Switches 7 and 8 on SW2 are both set to on, so the adapter reads

the data rate from parameter 5.

Refer to Chapter 2, Configuring the 1203-GK5 Module or 1336-GM5
Board
, for more information.

Parameter Number

3

Parameter Type

Read Only

Factory Default

125 kbps

Minimum Value

0

Maximum Value

3

Units

0 = 125
1 = 250
2 = 500
3 = Program using network

Power Cycle Required

No

When set to this position, the data rate and node address are programmed over
the DeviceNet network using DeviceNet Manager software.