DeviceNet Objects (Class Code 0x10 — Parameter Group Object)

Class Code 0x10 — Parameter
Group Object

The Parameter Group Object identifies and provides access to groups
of parameters in a device grouping. The Parameter Group Object
provides convenient access to related sets of parameters.

Class Attributes

Instances

The number of instances varies based on the number of groups in the
SCANport product. One additional group is added for the module.

Instance Attributes

Attribute

ID

Access

Rule

Name

Data

Type

Description

1

Get

Parameter
group version

UINT

Returns 1

2

Get

Max Instance

UINT

Maximum instance number of
an object currently created in
this class level of the device.

8

Get

Native
Language

USINT

Language ID for all STRING
accesses.
0 = English
1 = French
2 = Spanish (Mexican)
3 = Italian
4 = German
5 = Japanese
6 = Portuguese

Instance

Description

1 – (n - 1)

SCANport product groups

n

Module group

n is the value returned by a get from class attribute 2 (max instance).

Attribute ID

Access Rule

Name

Data Type

Description

1

Get

Group Name String

SHORT_

STRING

A text string representing the group name (e.g., set-up,
frequency set).
Maximum number of characters = 16

2

Get

Number of Members in
Group

UINT

Number of parameters in group.

3

Get

1st Parameter Number
in Group

UINT

Parameter instance number.

4

Get

2nd Parameter Number
in Group

UINT

Parameter instance number.

n

Get

(n-2)th Parameter
Number in Group

UINT

Parameter instance number.