3-8

Installing the 1203-GK5 Module or 1336-GM5 Board

Installing the 1336-GM5 Communications Board

The following instructions explain how to physically install a
DeviceNet 1336-GM5 communications board.

Important: If you are attaching the communications board to a 1336
PLUS II, refer to the one-page insert included with the kit for
mounting instructions.

Important:

To prevent damage to the board, you must wear a

grounding wrist strap when handling the 1336-GM5 communications
board.

1. Remove power from the product, and verify that the drive is not

holding power.

2. Remove power from the DeviceNet network.

3. Screw the four stand-off nylon headers into the appropriate

spaces on the drive main control board.

Figure 3.7
Mounting the Open Style Communications Board

!

ATTENTION: Remove all power from the SCANport
product before installing the 1336-GM5 board. Failure
to disconnect power may result in death or serious injury.
Verify all power is removed before installing the
1336-GM5 board.

DeviceNet

Connector

Internal SCANport

Connector

Black - V -

Blue - CAN_L

Bare - Shield

White - CAN_H

Red - V+

DeviceNet Status
SCANport Status

AB0945