Chapter

2

Configuring the 1203-GK5 Module or
1336-GM5 Board

Chapter Objectives

Chapter 2 provides instructions and information that you need to
configure the 1203-GK5 module or 1336-GM5 board. In this chapter,
you will read about the following:

Factory-default settings.

Configuring the adapter.

Factory-Default Settings

The 1203-GK5 and 1336-GM5 are shipped with these settings:

16-bit logic command/status enabled for polling.

16-bit reference/feedback enabled for polling.

If the scanner is put into program mode or the network fails, the
SCANport product is faulted by the module.

A node address of 63.

DeviceNet data rate of 125K.

Locating the DIP Switches

To configure the 1203-GK5 module or 1336-GM5 board, you must
set their DIP switches. On the 1203-GK5 module, DIP switches are
found in the following location.

Figure 2.1
Switches on the 1203-GK5 Module

AB0939

Bottom View

SW2.1 – SW2.6 = Node Address Selection
SW2.7 – SW2.8 = Data Rate Selection

SW1.1 = Datalink A
SW1.2 = Datalink B
SW1.3 = Datalink C
SW1.4 = Datalink D
SW1.5 = Not Used
SW1.6 = Zero Data / Hold Last State
SW1.7 = Fault on Comm Loss
SW1.8 = Fault On Pgm / Idle

Advertising