Class attributes instance attributes – Rockwell Automation 1203-GK5 DeviceNet Communications Module FRN 1.xxx-3.xxx User Manual

Page 113

Advertising
background image

DeviceNet Objects (Class Code 0x98 — SCANport Pass-Through Warning Object)

C-23

Class Code 0x98 — SCANport
Pass-Through Warning Object

The SCANport Pass-Through Warning Object provides information
on the product’s warning queue.

Class Attributes

Instance Attributes

Attribute

ID

Access

Rule

Name

Data Type

Description

0

Set

Write
Warning
Command

BYTE

Write Warning Command.
1 = Clear Warnings
2 = Clear Warning Queue
3 = Reset Product

1

Set

Read Number
of Warning
Queue
Entries

BYTE

Attribute

ID

Access

Rule

Name

Data Type

Description

0

Get

Read
Warning
Queue Entry
Full/All Info

STRUCT of

Warning Text

ARRAY of

BYTE

16 character string (no length
information, no terminating
null).

Warning
Code

WORD

Fault Code.

Warning Time
Stamp (Time
Stamps not
available in all
products)

STRUCT

BYTE

1/100 Second (0 – 99).

BYTE

Second (0 – 59).

BYTE

Minute (0 – 59).

BYTE

Hour (0 – 23).

BYTE

Day of Week (0 – 6).

BYTE

Date (1 – 31).

BYTE

Month (1 – 12).

BYTE

Year (0 – 99

).

Sunday is a value of zero.

Year is an offset from 1990.