6-2

Using DeviceNet Explicit Messages

Messaging for the 1771-SDN
Scanner

The PLC uses a 64-word Block Transfer Write (BTW) to copy an
Explicit Message into the 1771-SDN scanner. Ten explicit message
buffers are available within the 1771-SDN scanner. When the BTW
completes, the scanner executes the message. The PLC must then poll
the scanner by performing a 64-word Block Transfer Read (BTR) to
complete the message. (Note that the PLC can transfer two Explicit
Messages per BTW or BTR and the scanner can have up to 10
Explicit Messages active at any time.)

When the BTR completes, the data received by the PLC will contain
information about the status of the current Explicit Message being
processed by the scanner. If an Explicit Message has completed, the
STATUS code in the Explicit Message Response is set to 1 and the
response message contains the data requested.

If the message status indicates that it is not completed, the BTR
should be repeated until the message is complete.

The format of Request and Response messages is in Figure 6.1.

Figure 6.1
Format of DeviceNet Messages

Format of 64-word Block Transfer

Write for Explicit Message Request

Format of 64-word Block Transfer

Read for Explicit Message Response

15

0

15

0

Transaction #1
Header (3 words)

TXID

COMMAND

TXID

STATUS

word 0

PORT

SIZE

PORT

SIZE

SERVICE

MAC ID

SERVICE

MAC ID

CLASS

SERVICE RESPONSE DATA

INSTANCE

"

ATTRIBUTE

"

SERVICE DATA

"

"

"

word 31

Transaction #2
Header (3 words)

TXID

COMMAND

TXID

STATUS

word 32

PORT

SIZE

PORT

SIZE

SERVICE

MAC ID

SERVICE

MAC ID

CLASS

SERVICE RESPONSE DATA

INSTANCE

"

ATTRIBUTE

"

SERVICE DATA

"

"

"

word 63