Table 8.a – altitude settings, Dip sw1, Altitude (m) – Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 107: 1000 to 0, 0 to 1000, 1001 to 2000, Table 8.b – drop out time settings, Drop out time, 50 ms, 75 ms

Advertising
background image

8-2

Configuration/Programming

1503-UM054C-EN-P – June 2013















This set of switches defines the amount of time, after an OPEN

command has been issued, when the contactor actually drops out.

This setting may be overridden by the DeviceNet parameter

associated with each IntelliVAC base. See Appendix B for a

description.

Table 8.B – Drop Out Time Settings

DROP OUT TIME

DIP SW1

4

5

6

50 mS

OFF

OFF

OFF

75 mS

OFF

OFF

ON

100 mS

OFF

ON

OFF

130 mS

OFF

ON

ON

150 mS

ON

OFF

OFF

175 mS

ON

OFF

ON

200 mS

ON

ON

OFF

240 mS

ON

ON

ON

Note:

The drop off time would be 6mS longer if the close command

is applied on IB.








Table 8.A – Altitude Settings

ALTITUDE

(m)

DIP SW1

1

2

3

-1000 to 0

OFF

OFF

OFF

0 to 1000

OFF

OFF

ON

1001 to 2000

OFF

ON

OFF

2001 to 3000

OFF

ON

ON

3001 to 4000

ON

OFF

OFF

4001 to 5000

ON

OFF

ON

Not defined

ON

ON

OFF

Not defined

ON

ON

ON

Contactor Drop

Out Time