Test mode status, Ibx out a status, Ibx out b status – Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 155: Fault status, Ibx- healthy module contactor open, Ibx-healthy module contactor closed, Ibx-invalid command present

Advertising
background image

9-32

DeviceLogix

1503-UM054C-EN-P – June 2013


Test Mode Status

This is a dual function bit which can be used to describe the status of

a selector switch which chooses between normal operation, and test

operation mode.


IBX Out A Status

This is a bit which describes the status of its respective IntelliVAC

Output A (close coil) output, a “1” indicated the output is energized

and the contactor closed. A “0” indicates the output is not energized

and the contactor may or may not be open dependent on contactor

type (Electrically held vs. mechanically latched)

IBX Out B Status

This is a bit which describes the status of its respective IntelliVAC

Output B (Open coil for mechanically latched contactors). A “1”

indicates an energized output resulting in the opening of a

mechanically latched contactor. A “0” indicates an output which is

not energized.


Fault Status

This is a bit which describes the fault status of the IntelliVAC Plus

module. If any of the fault states exist in the module this bit will “1”

otherwise it will be “0”

IBX- Healthy Module Contactor open

This is a bit which describes the health status of its associated

IntelliVAC base module. If there are no faults on the module and

the contactor is open this bit will be “1”. The bit will be “0” of there

is a fault present on the IB module.


IBX-Healthy Module Contactor closed

This is a bit which describes the health status of its associated

IntelliVAC base module. If there are no faults on the module, and

the contactor is closed this bit will be “1”. The bit will be “0” if

there is a fault present on the IB module.


IBX-Invalid Command Present

This bit is set when an invalid command is present on the module.

For example if both an open and close command is given

simultaneously.