Grounding, Connections – Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 77

Advertising
background image

5-2

IntelliVAC Plus Basic Wiring

1503-UM054C-EN-P – June 2013

Grounding

The IntelliVAC module must be connected to a common ground

terminal (PE) on the controller panel. The ground terminal is located

on the bottom of module enclosure (refer to Figure 5.1).

A T T E N T I O N

A T T E N T I O N

It is important that IntelliVAC is properly

grounded using the ground connection

provided. Failure to do so may result in

damage to equipment or personal injury.


Connections

There are five green connectors on the IntelliVAC Plus module for

connections to the control circuitry. Connector plugs are provided

with the module. If additional plugs are required, refer to Appendix

D, Spare parts.

Control Power

The IntelliVAC can accept either AC or DC control power. Refer to

Table 1.B for acceptable input power and control signal ratings.

Control power is applied to the module with a two-pole connector

located at the bottom rear portion of the module. Refer to Figure 5.1

for connections. The ‘L1’ connection is intended to be the ‘Hot’ or

‘+’ side of the control power, and the ‘L2/N’ connection is intended

to be the ‘Neutral’, ‘Return’, or ‘-’ side of the control power.

Status Relays

Status relay connections are accessed with a four-pole connector

located at the bottom front portion of the module. Refer to Figure

5.1 for connections. There are two status relays, each with one

normally-open contact:

Module Status:

Terminals 13 and 14

Contactor Status: Terminals 15 and 16

L2/N

L1

CONTACTOR STATUS OUTPUT (N.O.)

MODULE STATUS OUTPUT (N.O.)

POWER INPUT

13 14 15 16

Ground Connection

Figure 5.1 – IntelliVAC Base Bottom Side Connections