DeviceLogix

1503-UM054C-EN-P – June 2013


Net Out9/Speed SW FWD Status

This is the output portion of the Speed SW FWD Status dual

function bit.


Net out 10/Speed SW REV Status

This is the output portion of the Speed SW REV Status dual function bit.


Net Out 11/Isolation SW status

This is the output portion of the Isolation SW status dual function bit.


Net Out 12/Remode Mode Status

This is the output portion of the Remote Mode Status dual function bit.


Net Out 13/Local Mode Status

This is the output portion of the Local Mode Status dual function bit.

Net out 14/ Normal Mode Status

This is the output portion of the Normal Mode Status dual function bit.


Net Out 15/Test Mode Status

This is the output portion of the Test Mode Status dual function bit


Net out 16, 18, 20, 22, 24/ IBX Trip Coil

These bits represent the “Trip” or “Open” coil for a mechanically

latched contactor. Setting this bit will result in opening a

mechanically latched contactor.


Net Out 17, 19, 21, 23, 25/ IBX Close coil

These bits represent the “Close” coil for both the mechanically

latched and electrically held contactors. For an electrically held

contactor the contactor is closed when the bit is set, and opens when

the bet is reset. For a mechanically latched contactor the bit is

pulsed to close the contactor and does not require to be maintained

set for the contactor to remain closed.


Net Out 26/Stop Status

This is the output portion of the “Stop Status” dual function bit.


Net Out 27/Start