Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 212

Advertising
background image

Parameters B-37

1503-UM054C-EN-P – June 2013

IntelliVAC Plus Action on Loss of DeviceNet Communications
[Loss Communication Action]

Parameter Number:

68,56,44,32,19.

Access rule:

Get/Set

Data Type:

BOOL

Object Mapping:

0xB4-1-125

Group:

Control

Units:

-

Minimum Value:

Hold

Maximum Value:

Reset

Default Value:

Hold

This parameter allows the user to view, as well as to select, the

control action which occurs after a loss of DeviceNet

communications occurs. There are two different actions that can be

selected, either Hold or Reset.

A detailed description for each of the Loss of Communications

Actions can be found in Chapter 7, DeviceNet Communications

Loss.


Control Bits Which Consumed on DeviceNet
[Consumed Net Work Bits]
Parameter Number:

69,57,45,33,20.

Access rule:

Get

Data Type:

WORD

Object Mapping:

0x4-3-3

Group:

Control

Units:

-

Minimum Value:

-

Maximum Value:

-

Default Value:

None

This parameter allows the user to view the status of the sixteen (16)

DeviceNet Consumed Network bits. Each bit position of the

parameter defines the state of one of the consumed network bits.

For each of the Consumed Network Bit’s listed, a status of ‘0’

indicates that the bit is disabled and a status of ‘1’ indicates that the

bit is enabled.