Troubleshooting

1503-UM054C-EN-P – June 2013

Table 10.A – IB Operational Troubleshooting Procedures (cont.)

LED Color

State

Condition/Possible Cause

Corrective Action

Module

Status

Contactor

Status

Yellow

Yellow

Warning

The mechanical latch contactor failed to

trip.
Trip command not present.

Contactor Auxiliary status missing


Trip coil open

Check that the Trip command is present

on the Trip input and that the voltage is

greater than or equal to the minimum

level listed in the Electrical Specifications

section.
Check that the Contactor Auxiliary status

connection between the contactor and

TB2-11/1,2 on the IntellilVAC Plus is

correct.
Check that there is not a Trip Coil open

message fault on DeviceNet or that the

Coil Open fault is not present on the Plus

Status LED. This could be caused by a

bad (open) coil or an open coil

connection.








Red

2 flash

Yellow

Fault

Power up with contactor Closed.

Contactor Auxiliary status missing

Contactor Auxiliary status contact bad

Contactor bottles bad

Obstruction in contactor

Check that the Contactor Auxiliary status

connection between the contactor and

TB11/1,2 on the IntelliVAC Plus is correct.
Check that the contactor Auxiliary status

contacts are functioning.
Check that the contactor bottles are not

welded closed.
Check that there is not an obstruction (or

possible binding in the contactor pivot

points) in the contactor which prevents

the bottle armature from opening.

Yellow -

Red

1 flash

Off/Yellow

(depends

on status

of

contactor)

Warning

Contactor fails to pick up

Contactor Auxiliary status missing

Obstruction in contactor

1. Check that the Contactor Auxiliary

status connection between the

contactor and TB11/1,2 on the

IntelliVAC Plus is correct.

2. Check that there is not an obstruction

(or possible binding in the contactor

pivot points) in the contactor which

prevents the bottle armature from

closing.

Yellow -

Red

2 flash

Off/Yellow

(depends

on status

of

contactor)

Warning

Contactor drop out during hold
Contactor Auxiliary status missing


Faulty contactor coil

1. Check that the Contactor Auxiliary

status connection between the

contactor and TB11/1,2 on the

IntelliVAC Plus is correct.

2. Check the condition of the main

contactor coil.