Configuration/Programming 8-5

1503-UM054C-EN-P – June 2013

This function is useful for applications that require a contactor to re-

close after a voltage dip or voltage loss.

This setting is used exclusively to determine the Power-up safety

mode. It cannot be set on the IE module, but can be read from the IB

module.

Table 8.F – Power-Up Safety Configuration

Power-up Safety

DIP SW2

6

Enabled

OFF

Disabled

ON

Future Use

These DIP switches are not used and are for future use.

Table 8.G – Future Use

Future Use

DIP SW2

7

8

Not used

OFF

OFF

Not used

OFF

ON

Not used

ON

OFF

Not used

ON

ON


MC Board DIP Switches

Some of the functionality of the IntelliVAC MC product is derived

from the settings of the DIP switches on the MC board.

The DIP switch settings are only read once after a power up

sequence occurs. If changes are to be made to the DIP switch inputs,

then control power must be recycled before the changes will take

affect.

Figure 8.2 – MC Board Configuration DIP Switches