Figure 9.13 – assume data available, Assume data available (alternate method), Forcing – Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 148

Advertising
background image

DeviceLogix 9-25

1503-UM054C-EN-P – June 2013

Note:

A double arrow will appear on the connection for which data

has been assumed available to indicate its status.

Figure 9.13 – Assume Data Available

Assume Data Available (alternate method)

There is an alternate technique for creating feedback loops. It is

recommended that this method be used for more complex feedback

loops, or for bits which must be fed back to multiple input locations.

The alternative method makes use of the dual bit functionality of the

“Interim 1-5” bits. In order use the alternate method connect the

output portion of the dual function bit to the output of bit to be fed

back, then simply connect the input portion of the bit to be fed back

to the feedback input. Figure 9.14 illustrates the same logical

implementation of as figure 9.13 using this alternative method. For

further information regarding dual function bits refer to “Dual

Function Bits” description further in this chapter.

Figure 9.14 – Assume Data Available Alternate Method

Forcing

The DeviceLogix Function Block Editor provides troubleshooting

capabilities by allowing you to force inputs and outputs that allow

you to verify the run time result of your logic.

To aid in troubleshooting and debugging your schematic, you can

force hardware inputs, and outputs. No other inputs or outputs can be

forced within the Function Block Editor. Network inputs can be

forced in the device from where they originate. If you exit the

Function Block Editor with a force enabled, that force will remain in

effect until you remove it.

Advertising