Appendix e_devicenet info, Appendix, Devicenet information – Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 366: Identify object

Advertising
background image

Appendix

E

1503-UM054C-EN-P – June 2013

DeviceNet Information



Identify Object

Table E.1 - Class Attributes

Attribute ID

Access

Rule

Name

DeviceNet Data

Type

Data Value

1

Get

Revision

UINT

1.0

2

Get

Max Instance 

UINT

1

Only valid when flash instance is supported.


Number of Instances: 1


Table E.2 – Instance Attributes

Attribute ID

Access

Rule

Name

DeviceNet

Data Type

Data Value

1

Get

Vendor ID

UINT

1= RA

2

Get

Device Type

UINT

115=Rockwell Misc.

3

Get

Product Code

UINT

263=4010P1 option

264=4010P2 option

265=4010P3 option

266=4010P4 option

267=4010P5 option

4

Get

Revision

STRUCT of:

Major Revision

USINT

1

Minor Revision

USINT

0

5

Get

Status

WORD

Device status*

6

Get

Serial Number

UDINT

Unique 32 bit number

7

Get

Product Name
String length
ASCII string

Structure of:
USINT
STRING [9]

21 “IntelliVAC Plus w/ 1IB”
~ “IntelliVAC Plus w/ 5IB”

8

Get

state

USINT

0 = Nonexistent

1 = Device Self Testing

2 = Standby

3 = Operational

4 = Major Recoverable Fault

5 = Major Unrecoverable Fault

9

Get

Configuration

Consistency

value

UINT

Unite value depending on output

of the parameter checksum

algorithm

10

Get/Set

Heartbeat

USING

0~255 (second)

Advertising