Contactor Fails to Drop Out

This is a Fault condition and the IntelliVAC Plus will not respond to

other commands until this condition is restored to normal. Check the

condition of the contactor or the Contactor Auxiliary Input.

This indicates that the Basic module within the IntelliVAC Plus unit

has a fault due to the contactor failing to drop out once the Close of

Jog command is removed (for Electrically Held Contactors) or a Trip

command has been issued (for Mechanically Latched Contactors)

and the status of the contactor being controlled is in an Open condition.

The contactor may actually have dropped out but required longer

than normal time to do so, having exceeded the time for a Long

Contactor Drop Out Time, which is set to 1S. Therefore, the

contactor required >1S for a Long Contactor Drop Out.

The Module status LED is flashing Red with 3 consecutive red

flashes followed by a pause to indicate a contactor that has not

dropped out at all or has required too long of a time to drop out and

the Module status relay is open to prevent externally connected

circuits from functioning.

The Contactor status LED is Red to indicate that the contactor has a

severe fault and has not dropped out at all, or at least not within the

maximum allowed time of 240mS and the Contactor status relay is

Open to prevent externally connected circuits from functioning.

This condition is valid for both Electrically Held and Mechanically

Latched contactors.

RS485 Communications Error

This is a Fault condition and the IntelliVAC Plus will not respond to

other commands until this condition is restored to normal. Check the

condition of any external RS485 cables/resistor terminators that may

be connected.

This indicates that the Basic module within the IntelliVAC Plus unit

has a fault due to RS485 communications errors between itself and

the IE unit and the status of the contactor being controlled is in an

Open condition.

The Module status LED is flashing Red with 4 consecutive red

flashes followed by a pause to indicate that there is an RS485

communications error with the commanding IE unit and the Module

status relay is open to prevent externally connected circuits from

functioning.