Configuration/Programming 8-3

1503-UM054C-EN-P – June 2013


Contactor Type

This set of switches defines the type of vacuum contactor that is to

be controlled.

Note:

These settings are used exclusively to determine the

contactor type. These setting cannot be set on the

IntelliVAC Plus module but can only be read from the IB

module.

Table 8.C – Contactor Type

CONTACTOR CONFIGURATION

DIP SW1

DIP SW2

7

8

1

2

400A Mech. Latch (7.2kV)

OFF

OFF

OFF

OFF

400A Elec. Held (7.2kV)

OFF

OFF

OFF

ON

800A Mech. Latch (7.2kV)

OFF

OFF

ON

OFF

800A Elec. Held (7.2kV)

OFF

OFF

ON

ON

Not Allowed

OFF

ON

OFF

OFF

Not Allowed

OFF

ON

OFF

ON

Not Allowed

OFF

ON

ON

OFF

Not Allowed

OFF

ON

ON

ON

Not Allowed

ON

OFF

OFF

OFF

Not Allowed

ON

OFF

OFF

ON

Not Allowed

ON

OFF

ON

OFF

Not Allowed

ON

OFF

ON

ON

Not Allowed

ON

ON

OFF

OFF

Not Allowed

ON

ON

OFF

ON

Not Allowed

ON

ON

ON

OFF

Not Allowed

ON

ON

ON

ON


Time Delay Undervoltage Enable (TDUV)

This setting determines whether the contactor maintains closed

during the occurrence of an input line voltage dip or brief power

outage. An undervoltage will occur when the input line decreases to

<95Vrms, just before a Close cycle is initiated or the input line

decreases to <80Vrms during the Hold cycle.

This setting is used exclusively to determine the TDUV

Configuration. This setting cannot be set on the IE module but can

only be read from the IB module.

Table 8.D – TDUV Configuration

TDUV Configuration

DIP SW2

3

TDUV disabled

OFF

TDUV enabled

ON