Up down counter – Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 142

Advertising
background image

DeviceLogix 9-19

1503-UM054C-EN-P – June 2013

Figure 9.9 – Timing Diagram for the Counter Function with a Preset Value = 3

Table 9.G – Count Up Timer Valid Data Ranges

Parameters

Data Range

PRE

0 ~ 65535

ACC

0 ~ 65535

Up Down Counter

The UP/DOWN counter has three inputs called Input, Reset, and

count down, and one output called output. The counter increments

the accumulator any time the input changes from FALSE to TRUE

and decrements the counter any time the counter down input changes

from FALSE to TRUE. When the accumulator falls below the

preset, the counter resets its output to false. Like the up counter, the

UP/DOWN counter resets when a TRUE level is detected on the

reset input. When a reset occurs, the counter zeroes the accumulator

and sets the output to FALSE