Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 342

Advertising
background image

Parameters B-167

1503-UM054C-EN-P – June 2013

Module Status of IB1 [IB Status]

Parameter Number:

323,265,207,149,90.

Access rule:

Get

Data Type:

BYTE

Object Mapping:

0xB4-1-120

Group:

Diagnostics

Units:

-

Minimum Value:

0

Maximum Value:

0xFF

Default Value:

0

This parameter allows the user to view the Module Status of IB1.

Table B.38 – Module Status of IB1

Bit

Enum Text

Description

0

Bit 0: Test Mode

IB1 in Test Mode

1

Bit 1: Normal Mode

IB1 in Normal Mode

2

Bit 2: Local Mode

IB1 in Local Mode

3

Bit 3: Remote Mode

IB1 in Remote Mode

4

Bit 4: Isolation SW

IB1 Isolation SW

5

Bit 5: Speed REV

IB1 in REV Speed

6

Bit 6: Speed FWD

IB1 in FWD Speed

7

Bit 7: Protection

IB1 in Protection Mode

See “Status Inputs” in DeviceLogix, Chapter 9 for an explanation of

each of those bits.


Run the DeviceLogix Module [Run DeviceLogix]

Parameter Number:

324,266,208,150,91.

Access rule:

Get/Set

Data Type:

BOOL

Object Mapping:

0x30E-1-1

Group:

Diagnostics

Units:

-

Minimum Value:

0 = Stop DeviceLogix Program

Maximum Value:

1 = Run DeviceLogix Program

Default Value:

0

This parameter allows the user to view and set the operating mode

for the DeviceLogix Module that has been selected. If the bit is a

‘0’ then the selected DeviceLogix Program will be Stopped. If the

bit is a ‘1’ then the selected DeviceLogix Program will be Run.