Figure 9.11 – modify function block attributes, Online animation, Change logic – Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 145

Advertising
background image

9-22

DeviceLogix

1503-UM054C-EN-P – June 2013

Figure 9.11 – Modify Function Block Attributes


In order to change a value:

1. Double-Click on the face of the function block you want to change.

2. Select Parameters tab

3. Locate the value that you want to change (values which can be

changed are white). Enter the new value in the box

4. Click OK. The new value takes immediate effect. If you are

changing a preset, remember to Save the configuration the next

time you exit from the Function Block Editor

.

Online Animation

Once you go online and the Logic Enable is set to ON, online

animation starts. The status of the I/O can be seen in the Function

Block Editor schematic. Note that in the online animation mode you

cannot edit instructions.

Change Logic

While the Function Block Editor is running and animated, you can

change the logic that appears on the schematic by first pressing the

Edit button or selecting Tools> Edit. When you change the logic,

the Function Block Editor will change from the animated mode into

Pending Edits mode. The logic in the device will not be affected and

the current program will continue to run. However, the screen will

not reflect the real-time status of the logic. The data on the wires

will be frozen to whatever it was when you modified the logic. To

ensure your changes take effect, perform the following steps:

Advertising