Step 2 - Plan the Installation

1329I-5.5 Integrated Drive/Motor — January, 2000

Planning the installation is necessary to ensure you have acceptable environmental and
operating conditions for the unit. Read and follow the requirements given below before
proceeding with the installation:

• Locate the unit where it will have unrestricted clearance as shown in Figure 2.2.

• Locate the unit where it will be kept clean (away from oil, coolants, or airborne

contaminants). The 1329I unit has an IP54/NEMA Type 12 rating. An IP rating
designates the enclosure’s level of protection. The first number in the rating (5)
indicates that the 1329I unit is dust-resistant. The second number (4) indicates that
the unit is splashproof.

• Mount the unit on a flat surface.

• Verify that the ambient temperature will remain between 0

˚

C to 40

˚

C (32

˚

F to

104

˚

F).

• Verify that the relative humidity will be between 5 percent and 95 percent,

non-condensing.

• For installations above 1000 meters (3300 feet), refer to Appendix A for derating

guidelines.

• Verify that there will be adequate clearance for opening the cover. See Figure 2.2.

• Verify that there will be adequate clearance for blower intake. See Figure 2.2.

Figure 2.2
Access Clearances

RESET

10.25 in

1.3 in

1 in

3 in

Cover Clearance

Blower Intake
Clearance