Step 10 - set the operating speed, Chapter 10, Chapter – Rockwell Automation 1329I Integrated AC Drive/Motor, Series B FRN 3.X User Manual
Page 53
1329I-5.5 Integrated Drive/Motor — January, 2000
Chapter
10
Step 10 - Set the Operating Speed
Before starting the unit, set the operating speed as follows:
Standard units: Use the speed potentiometer or other user-supplied external speed
reference device.
Local operator control units: As shipped from the factory, the unit receives its speed
reference from the keypad. Use the
key to increase the speed reference and the
key to decrease the speed reference.
To use the analog input terminals for the speed reference, setup switch 2 (Speed
Reference Select) must be in the ON position. In this case, the
keys are not
used. Refer to Section 8.3.2 for more information.
Important:
At subsequent power ups, the unit will use the last speed reference setting
selected before power was removed.