Speed reference select (position 2) -6 – Rockwell Automation 1329I Integrated AC Drive/Motor, Series B FRN 3.X User Manual

Page 44

Advertising
background image

8-6

Step 8 - Verify the Setup and Adjust Switches if Required

1329I-5.5 Integrated Drive/Motor — January, 2000

The switch at position 1 enables or disables the run on power up function. When this
function is enabled, output power is applied to the Motor Section automatically at power
up if all run on power up permissive conditions are met. These conditions are:

• No faults are active.

• The terminal strip function loss input is closed.

In terminal block start mode: In addition to the start permissive conditions listed

above, the terminal strip Start and Stop inputs must be closed.

In operator control start mode: The unit will simulate a start signal edge; you do

not have to press the green

key.

Settings (Position 1):

OFF position (Default) = Run On Power Up Disabled
ON position = Run On Power Up Enabled

8.3.2 Speed Reference Select (Position 2)

Important:

This applies only to local operator control units.

The switch at position 2 is used to select whether the unit gets its speed reference from
the operator controls or from the analog input terminals. If this switch is set to the OFF
position, the speed reference will come from the operator controls. If this switch is set
to the ON position, the speed reference will come from the analog input terminals, and
the

and

keys are not functional.

Settings (Position 2):

OFF position (Default) = Speed Reference from Operator Controls
ON position = Speed Reference from Analog Input Terminals

8.3.3 Relay Control Output - Running or Faulted (Position 3)

The switch at position 3 specifies the type of status indication provided by the normally
open (N.O.) relay control output (control terminals 19 and 20). See Section 7.3 for a
description of control terminals 19 and 20. The relay can be used to indicate that the
unit is running (power is applied to the Motor Section) or has faulted (an active drive
fault exists).

Settings (Position 3):

OFF position = Unit Running Indication (Default)
ON position = Unit Faulted Indication

Switch 3 Position

State of Unit

Relay Control

Output Status

OFF (Unit running indication selected)

Running

Closed

Stopped

Open

ON (Unit faulted indication selected)

No Faults

Closed

Active Fault

Open