Auto restart (position 4) -7 – Rockwell Automation 1329I Integrated AC Drive/Motor, Series B FRN 3.X User Manual

Page 45

Advertising
background image

Step 8 - Verify the Setup and Adjust Switches if Required

8-7

1329I-5.5 Integrated Drive/Motor — January, 2000

8.3.4 Auto Restart (Position 4)

The switch at position 4 enables or disables the auto-restart function. If the auto-restart
function is enabled, the unit shuts down as usual upon the detection of a fault, waits five
seconds, and attempts to start automatically. If the fault reoccurs, the Drive Section
again waits five seconds before trying to start, up to a maximum of four attempts within
a five minute period. If the Drive Section fails all these attempts, it remains in the faulted
state and displays the fault it is attempting to clear.

Auto Restart Countdown

As a precaution, the drive will visually count down for 5 seconds prior to an auto restart
attempt. The following character groups are displayed in sequence to indicate that the
countdown is in progress.

Table 8.1
Auto-Restartable Faults

Settings (Position 4):

OFF position (Default) = Auto-Restart Disabled
ON position = Auto-Restart Enabled

ATTENTION: When this feature is enabled, the Drive Section will
restart automatically after an auto-restartable fault occurs (see Table 8.1).
This feature may only be used as outlined in NFPA79, Under Voltage
Protection for specialized applications. Equipment damage and/or
personal injury or loss of life may result if this feature is used in an
inappropriate application. An auto-restart can be canceled by pressing the

key or remote Reset device.

Fault Code

Description

Overcurrent

Overload

High bus voltage

Low bus voltage

Overtemperature

RESET

...

...

...

...